Delta Network Module (DVP02LC-SL)
Brand: Delta
Product Model: DVP02LC-SL
Specifications
Rated power supply voltage/power consumption 24 VDC (-15 to +20%)/3 W
Voltage boundary 18 to 31.2 VDC
Max. current consumption 125 mA
Input signal range +-40 mVDC
Sensibility +5 VDC +/-10%
Internal resolution 24 bits
Communication port RS-232, RS-485
Applicable sensor type 4-wire or 6-wire load cell
Temperature coefficient span <=+- 50 ppm/K v. E
Temperature coefficient zero
point
<= +- 0.4 uV/K
Linearity error <= 0.02%
Response time 2, 10, 20, 40, 80 ms × number of channels
4 measuring ranges 0 to 1, 0 to 2, 0 to 4, 0 to 6 mV/V
Max. distance for connecting
to load cell
100m
Max. current output 5 VDC × 300 mA
Permitted load cell
resistance
40 to 4,010 ?
Common mode rejection
(CMRR @50/60 Hz)
>= 100dB
Dynamic value filter Setting range: K1 to K5
Average value filter Setting range: K1 to K100
Isolation method 500 VAC between digital circuits and ground
500 VAC between analog circuits and ground
500 VAC between analog circuits and digital circuits
Serial connection to
DVP-PLC MPU
Connectable to the left side of the MPU, numbered from 100 to 107 according to the position of the module from the closest to the farthest to the MPU.
Operation/storage Operation: 0 to 55°C (temperature),50 to 95% (humidity), pollution
degree 2
Storage: -25 to 70°C (temperature), 5 to 95% (humidity)
Vibration/shock immunity International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)