Specification:
DVP24ES00T2 Delta PLC 100-240VAC 16DI 8DO transistor output Original brand new
Introduction:
DVP-ES/EX Series provide the main processing units and extension units. The processing units offer 14~60 points and the extension units offer 8~32 points. The maximum input and output can be extended up to 128 points respectively. Also, it can be used on various applications according to input and output points, power supply, digital input and output modules.
Electrical Specifications:
Model
Item
DVP14ES00_ DVP24ES00_ DVP32ES00_ DVP40ES00_ DVP60ES00_ DVP20EX00_ DVP14ES01_ DVP32ES01_ DVP20EX11_
Power Supply
Voltage
100~240VAC (-15%~10%), 50/60Hz +- 5% 24VDC (-15%~10%)
Operation
Specification
The PLC start to operate at power supply of 95~100VAC.
If the voltage of power supply drops to 70VAC, the PLC will stop.
Maximum power loss time is 10ms or less.
Maximum power loss time is 5ms or less.
Fuse 2 A / 250VAC 2 A / 250VAC
Power
Consumption
20VA 25VA 30VA 30VA 35VA 30VA 5.5W 8W 8W
DC24V Supply
Current
400mA 400mA 400mA 400mA 400mA 400mA — — —
Power
Protection
DC24V output short circuit DC24V input polarity
Voltage
Withstand
1500VAC(Primary-secondary), 1500VAC(Primary-PE), 500VAC(Secondary-PE)
Insulation
Resistance
>5 M ohm at 500VDC (Between all inputs / outputs and earth)
Noise Immunity ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
RS: 26MHz~1GHz, 10V/m
Grounding The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to the ground pole).
Environment Operation: 0°C ~55°C (Temperature), 50~95% (Humidity), Pollution degree2; Storage: -25°C ~70°C (Temperature), 5~95% (Humidity)
Vibration / Shock
Resistance
Standard: IEC1131-2, IEC 68-2-6(TEST Fc)/ IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight (g) 400 552 580 596 750 536 260 430 386